ARMORED CABLES
JACKETED MCACW90/ACWU90, 50% Ground600 Volt Copper4 Conductor

Description
Four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RW90), phase identified and cabled together with suitable fillers (when necessary) and bare copper ground conductor (3 segmented grounds). Cable core covered with mylar binder tape and galvanized steel interlocked armour, with overall black PVC jacket. Jacket available in colours.
Application
Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2
Standards
UL 1569
CSA C22.2 #51
ICEA S-95-658/NEMA WC-70
Flame Rated: CT Use, IEEE 383 (70,000 BTU), ICEA T-29-520
(210,000 BTU), IEEE 1202/CSA FT-4, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -25°C
Sunlight and Oil Resistant II Jacket
Direct Burial (includes encasement in concrete)
Color Code: Method 4 (optional color codes available)
RoHS Compliant
| Part Number
| Size | Strand | Insulation Thickness | Grounding Conductors | Diameter Over Armour | PVC Jacket Thickness | Approx. Diameter Overall | Approx. Net Weight | Ampacity* |
| GAP6/4G3#12 | 6 | 7 | 45 | (3) #12 | 0.87 | 50 | 0.97 | 778 | 75 |
| GAP4/4G3#10 | 4 | 7 | 45 | (3) #10 | 0.99 | 50 | 1.09 | 1,077 | 95 |
| GAP3/4G3#10 | 3 | 7 | 45 | (3) #10 | 1.05 | 50 | 1.15 | 1,248 | 115 |
| GAP2/4G3#8 | 2 | 7 | 45 | (3) #8 | 1.13 | 50 | 1.23 | 1,515 | 130 |
| GAP1/4G3#8 | 1 | 19 | 55 | (3) #8 | 1.33 | 50 | 1.43 | 1,933 | 145 |
| GAP1/04G3#6 | 1/0 | 19 | 55 | (3) #6 | 1.43 | 50 | 1.53 | 2,379 | 170 |
| GAP2/04G3#6 | 2/0 | 19 | 55 | (3) #6 | 1.51 | 60 | 1.63 | 2,829 | 195 |
| GAP3/04G3#4 | 3/0 | 19 | 55 | (3) #4 | 1.65 | 60 | 1.77 | 3,500 | 225 |
| GAP4/04G3#4 | 4/0 | 19 | 55 | (3) #4 | 1.79 | 60 | 1.91 | 4,167 | 260 |
| GAP250/4G3#4 | 250 | 37 | 65 | (3) #4 | 1.99 | 60 | 2.11 | 4,883 | 290 |
| GAP300/4G3#3 | 300 | 37 | 65 | (3) #3 | 2.13 | 60 | 2.25 | 5,743 | 320 |
| GAP350/4G3#2 | 350 | 37 | 65 | (3) #2 | 2.25 | 75 | 2.40 | 6,667 | 350 |
| GAP400/4G3#2 | 400 | 37 | 65 | (3) #2 | 2.35 | 75 | 2.50 | 7,381 | 380 |
| GAP500/4G3#1 | 500 | 37 | 65 | (3) #1 | 2.53 | 75 | 2.68 | 8,984 | 430 |
| GAP600/4G3-1/0 | 600 | 61 | 80 | (3) 1/0 | 2.85 | 75 | 3.00 | 10,795 | 475 |
| *Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances. | |||||||||