TRAY & POWER CABLES
TRAY CABLERW90/ServiceCPE®, Shielded600 Volt Copper3 or 4 Conductor
Resources

Description
Three or four stranded copper conductors, insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled together with fillers and bare copper ground conductor. Cable core covered with mylar binder tape, longitudinally applied corrugated copper tape shield, and overall black CPE jacket. Available with tinned conductors.
Application
Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2
Standards
UL1277
CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4
UL 1581, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -25°C
Sunlight and Oil Resistant I Jacket
Direct Burial
Color Code: Method 4
K-2 Solid Colors (#14 AWG - #10 AWG)
(optional color codes available)
RoHS Compliant
|
Part Number
|
Size |
Strand |
Insulation Thickness |
Grounding Conductor |
Jacket Thickness |
Approx. Diameter Overall |
Approx. Net Weight |
Ampacity* |
|||||||||
|
TCCPESHC14/3G |
14 |
7 |
30 |
14 |
45 |
0.40 |
134 |
25† |
|||||||||
|
TCCPESHC12/3G |
12 |
7 |
30 |
12 |
45 |
0.44 |
175 |
30† |
|||||||||
|
TCCPESHC10/3G |
10 |
7 |
30 |
10 |
45 |
0.49 |
233 |
40† |
|||||||||
|
TCCPESHC8/3G |
8 |
7 |
45 |
10 |
60 |
0.64 |
347 |
55 |
|||||||||
|
TCCPESHC6/3G |
6 |
7 |
45 |
8 |
60 |
0.72 |
505 |
75 |
|||||||||
|
TCCPESHC4/3G |
4 |
7 |
45 |
8 |
80 |
0.87 |
729 |
95 |
|||||||||
|
TCCPESHC2/3G |
2 |
7 |
45 |
6 |
80 |
0.99 |
1,045 |
130 |
|||||||||
|
TCCPESHC1/3G |
1 |
19 |
55 |
6 |
80 |
1.10 |
1,274 |
145 |
|||||||||
|
|
|||||||||||||||||
|
TCCPESHC14/4G |
14 |
7 |
30 |
14 |
45 |
0.43 |
158 |
25† |
|||||||||
|
TCCPESHC12/4G |
12 |
7 |
30 |
12 |
45 |
0.48 |
208 |
30† |
|||||||||
|
TCCPESHC10/4G |
10 |
7 |
30 |
10 |
60 |
0.56 |
295 |
40† |
|||||||||
|
TCCPESHC8/4G |
8 |
7 |
45 |
10 |
60 |
0.70 |
426 |
55 |
|||||||||
|
TCCPESHC6/4G |
6 |
7 |
45 |
8 |
60 |
0.79 |
618 |
75 |
|||||||||
|
TCCPESHC4/4G |
4 |
7 |
45 |
8 |
80 |
0.95 |
903 |
95 |
|||||||||
|
TCCPESHC2/4G |
2 |
7 |
45 |
6 |
80 |
1.08 |
1,309 |
130 |
|||||||||
|
*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-16 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances. |
|||||||||||||||||