TRAY & POWER CABLE

TRAY CABLE

XHHW-2 or RW90/EnviroPlus®

600 Volt Copper, Zero Halogen, Limited Smoke

Factory Mutual Group 1

Description

Conductors are stranded, annealed copper, insulated with heat and moisture resistant crosslinked polyethylene (type XHHW- 2 or RW90) and phase identified. Cabled with fillers (when necessary). Cable core is covered with binder tape and an overall black zero halogen, limited smoke, zero lead jacket. Available with non-tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2

Standards

UL1277, CSA C22.2 #230/#239 TC/CIC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL1685 and UL 1581, Two-hour Firewall
Temperature Rated 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: K-2 (optional color codes available)
Zero Halogen, Limited Smoke Jacket
RoHS Compliant

VIEW PRODUCT DATA TABLE

 

Part Number

 

 

Number of

Conductors

 

 

Overall

Jacket

(mils)

 

Nominal

Diameter

(in.)

 

Approx.

Net Weight

(lb./1000')

Ampacity*

(30°C ambient) 90°C Wet/Dry

TCNH14/2T

2

45

0.39

     70

  25†

TCNH14/3T

3

45

0.41

     90

  25†

TCNH14/4T

4

45

0.45

   111

  20†

TCNH14/5T

5

45

0.48

   133

  20†

TCNH14/7T

7

60

0.55

   189

  17†

TCNH14/9T

9

60

0.64

   236

  17†

TCNH14/12T

12

60

0.71

   299

12

TCNH14/19T

19

60

0.82

   439

12

TCNH14/37T

37

80

1.12

   841

10

 

TCNH12/2T

2

45

0.43

     91

  30†

TCNH12/3T

3

45

0.45

   120

  30†

TCNH12/4T

4

45

0.49

   151

  24†

TCNH12/5T

5

60

0.57

   199

  24†

TCNH12/7T

7

60

0.61

   258

  21†

TCNH12/9T

9

60

0.70

   324

  21†

TCNH12/12T

12

60

0.79

   414

15

TCNH12/19T

19

80

0.95

   656

15

TCNH12/37T

37

80

1.26

1,188

12

 

TCNH10/2T

2

45

0.48

   122

  40†

TCNH10/3T

3

45

0.50

   164

  40†

TCNH10/4T

4

60

0.58

   225

  32†

TCNH10/5T

5

60

0.63

   271

  32†

TCNH10/7T

7

60

0.68

   357

28

TCNH10/9T

9

60

0.79

   450

28

TCNH10/12T

12

80

0.92

   618

20

TCNH10/19T

19

80

1.07

   920

20

TCNH10/37T

37

80

1.42

1,692

16

*Per NEC Table 310.15 (B)(16). (Ampacity derated in accordance with note 8a.) †The overcurrent protection for items marked with an (†) shall not exceed 15 amps for #14 AWG, and 20 amps for #12 AWG and 30 amps for #10 AWG per NEC 310-16 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.