TRAY & POWER CABLES
TRAY CABLEXHHW-2 or RW90/ServiceCPE®600/1,000 Volt Copper3 Conductor

Description
Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled together with fillers (when necessary) and bare copper ground conductor. Cable core covered with binder tape and overall black CPE jacket. Available with tinned conductors.
Application
Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.
Standards
UL 1277
CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU),
T-29-520 (210,000 BTU) (available upon request),
IEEE 1202/CSA FT-4 (available upon request),
Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant, Gasoline and Oil Resistant I Jacket
Direct Burial
Color Code: Black and Numbered (#8 and larger)
K-2 Solid Colors (#14 AWG - #10 AWG)
(optional color codes available)
RoHS Compliant
|
Part Number
|
Size |
Strand |
Insulation Thickness |
Grounding Conductor |
Jacket Thickness |
Approx. Diameter Overall |
Approx. Net Weight |
Ampacity* |
|
|
TCCPE14/3G |
14 |
7 |
30 |
14 |
45 |
0.38 |
95 |
25† |
|
|
TCCPE12/3G |
12 |
7 |
30 |
12 |
45 |
0.42 |
133 |
30† |
|
|
TCCPE10/3G |
10 |
7 |
30 |
10 |
45 |
0.47 |
188 |
40† |
|
|
TCCPE8/3G |
8 |
7 |
45 |
10 |
60 |
0.62 |
292 |
55 |
|
|
TCCPE6/3G |
6 |
7 |
45 |
8 |
60 |
0.72 |
451 |
75 |
|
|
TCCPE4/3G |
4 |
7 |
45 |
8 |
80 |
0.87 |
666 |
95 |
|
|
TCCPE3/3G |
3 |
7 |
45 |
6 |
80 |
0.92 |
816 |
115 |
|
|
TCCPE2/3G |
2 |
7 |
45 |
6 |
80 |
0.99 |
973 |
130 |
|
|
TCCPE1/3G |
1 |
19 |
55 |
6 |
80 |
1.10 |
1,193 |
145 |
|
|
TCCPE1/03G |
1/0 |
19 |
55 |
6 |
80 |
1.19 |
1,447 |
170 |
|
|
TCCPE2/03G |
2/0 |
19 |
55 |
6 |
80 |
1.28 |
1,754 |
195 |
|
|
TCCPE3/03G |
3/0 |
19 |
55 |
4 |
80 |
1.39 |
2,179 |
225 |
|
|
TCCPE4/03G |
4/0 |
19 |
55 |
4 |
80 |
1.51 |
2,661 |
260 |
|
|
TCCPE250/3G |
250 |
37 |
65 |
4 |
80 |
1.63 |
3,073 |
290 |
|
|
TCCPE350/3G |
350 |
37 |
65 |
3 |
110 |
1.90 |
4,273 |
350 |
|
|
TCCPE500/3G |
500 |
37 |
65 |
2 |
110 |
2.17 |
5,901 |
430 |
|
|
TCCPE600/3G |
600 |
61 |
80 |
2 |
110 |
2.40 |
7,039 |
475 |
|
|
TCCPE750/3G |
750 |
61 |
80 |
1 |
110 |
2.61 |
8,662 |
535 |
|
|
*Per NEC Table 310.15 (B)(16). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-16 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances. |
|||||||||