TRAY & POWER CABLES

TRAY CABLE

RW90/EnviroPlus®

1,000 Volt Copper, LSZH Jacket

4 Conductor, Factory Mutual Group 1

Description

4 conductors, stranded copper, insulated with heat and moisture resistant crosslinked polyethylene (type USE-2 or RW90 1kV) and phase identified. Cabled with fillers and bare copper ground conductor. Cable core is covered with binder tape and overall black low smoke, zero halogen, lead-free jacket.
Available with tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2

Standards

UL1277, CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4
       UL1685 and UL 1581, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: Method 4 (optional color codes available)
Low Smoke, Zero Halogen Jacket
RoHS Compliant

VIEW PRODUCT DATA TABLE

 

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation

Thickness

(mils)

Grounding

Conductor

(AWG)

Jacket

Thickness

(mils)

Approx.

Diameter Overall

(in.)

Approx.

Net Weight

(lb./1000')

Ampacity*

(30°C ambient)

90°C Wet/Dry

TCNH8/4G

8

  7

  60

10

  60

0.79

      408

  55

TCNH6/4G

6

  7

  60

  8

  80

0.92

     645

  75

TCNH4/4G

4

  7

  60

  8

  80

1.04

     894

  95

TCNH3/4G

3

  7

  60

  6

  80

1.10

  1,086

115

TCNH2/4G

2

  7

  60

  6

  80

1.17

  1,294

130

TCNH1/4G

1

19

  80

  6

  80

1.35

  1,629

145

TCNH1/04G

1/0

19

  80

  6

  80

1.44

  1,975

170

TCNH2/04G

2/0

19

  80

  6

  80

1.55

  2,388

195

TCNH3/04G

3/0

19

  80

  4

110

1.73

  3,047

225

TCNH4/04G

4/0

19

  80

  4

110

1.87

  3,699

260

TCNH250/4G

250

37

  95

  4

110

2.02

  4292

290

TCNH350/4G

350

37

  95

  3

110

2.26

  5,760

350

TCNH500/4G

500

37

  95

  2

110

2.56

  7,921

430

TCNH600/4G

600

61

110

  2

140

2.88

  9,613

475

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE