TRAY & POWER CABLES
TRAY CABLERW90/EnviroPlus®1,000 Volt Copper, LSZH Jacket4 Conductor, Factory Mutual Group 1
Resources

Description
4 conductors, stranded copper, insulated with heat and moisture resistant crosslinked polyethylene (type USE-2 or RW90 1kV) and phase identified. Cabled with fillers and bare copper ground conductor. Cable core is covered with binder tape and overall black low smoke, zero halogen, lead-free jacket.
Available with tinned conductors.
Application
Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2
Standards
UL1277, CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4
UL1685 and UL 1581, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: Method 4 (optional color codes available)
Low Smoke, Zero Halogen Jacket
RoHS Compliant
|
Part Number
|
Size (AWG or Kcmil) |
Strand (no.) |
Insulation Thickness (mils) |
Grounding Conductor (AWG) |
Jacket Thickness (mils) |
Approx. Diameter Overall (in.) |
Approx. Net Weight (lb./1000') |
Ampacity* (30°C ambient) 90°C Wet/Dry |
|
|
TCE8/4UG |
8 |
7 |
60 |
10 |
60 |
0.79 |
408 |
55 |
|
|
TCE6/4UG |
6 |
7 |
60 |
8 |
80 |
0.92 |
645 |
75 |
|
|
TCE4/4UG |
4 |
7 |
60 |
8 |
80 |
1.04 |
894 |
95 |
|
|
TCE3/4UG |
3 |
7 |
60 |
6 |
80 |
1.10 |
1,086 |
115 |
|
|
TCE2/4UG |
2 |
7 |
60 |
6 |
80 |
1.17 |
1,294 |
130 |
|
|
TCE1/4UG |
1 |
19 |
80 |
6 |
80 |
1.35 |
1,629 |
145 |
|
|
TCE1/04UG |
1/0 |
19 |
80 |
6 |
80 |
1.44 |
1,975 |
170 |
|
|
TCE2/04UG |
2/0 |
19 |
80 |
6 |
80 |
1.55 |
2,388 |
195 |
|
|
TCE3/04UG |
3/0 |
19 |
80 |
4 |
110 |
1.73 |
3,047 |
225 |
|
|
TCE4/04UG |
4/0 |
19 |
80 |
4 |
110 |
1.87 |
3,699 |
260 |
|
|
TCE250/4UG |
250 |
37 |
95 |
4 |
110 |
2.02 |
4292 |
290 |
|
|
TCE350/4UG |
350 |
37 |
95 |
3 |
110 |
2.26 |
5,760 |
350 |
|
|
TCE500/4UG |
500 |
37 |
95 |
2 |
110 |
2.56 |
7,921 |
430 |
|
|
TCE600/4UG |
600 |
61 |
110 |
2 |
140 |
2.88 |
9,613 |
475 |
|
|
*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances. |
|||||||||