SINGLE CONDUCTORS
SERVICEPRO-X®RW90600 Volt Copper, FT-1No Pulling Lubricant Required

Description
Single copper conductor, stranded and insulated with moisture, heat, and flame resistant, chemically crosslinked polyethylene. ServicePRO-X® Insulation–No Pulling Lubricant Required (#6 AWG and larger). Available in colors.
Application
Suitable for general purpose wiring, power distribution, and branch circuit wiring where a cable having superior flame retardance is required. Suitable for use in 105°C dry systems. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).
Standards
ASTM Standards: B-3 (soft or annealed), B-8 (concentric lay stranded),
B-787 (combination strand)
UL 44, CSA RW90: Certified by CSA for use in Canada
CSA C22.2 No. 38
ICEA S-95-658/NEMA WC-70
Flame Rated: FT-1 (all sizes), CT Use/IEEE 1202 (1/0 AWG and larger),
FT-4 (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant (#6 AWG and larger), Gasoline and Oil Resistant II
Appliance Wiring Material: Style 3578
RoHS Compliant
|
Part Number
|
Size (AWG or Kcmil) |
Strand (no.) |
Insulation Thickness (mils) |
Nominal Diameter Overall (in.) |
Approx. Net Weight (lb./1000') |
Ampacity* 90°C Wet/Dry |
|
|
XHVW14BK |
14 |
7 |
30 |
0.133 |
19 |
35† |
|
|
XHVW12BK |
12 |
7 |
30 |
0.152 |
28 |
40† |
|
|
XHVW10BK |
10 |
7 |
30 |
0.175 |
41 |
55† |
|
|
XHVW8BK |
8 |
7 |
45 |
0.233 |
66 |
80 |
|
|
XHVW6BK |
6 |
7 |
45 |
0.271 |
102 |
105 |
|
|
XHVW4BK |
4 |
7 |
45 |
0.320 |
155 |
140 |
|
|
XHVW3BK |
3 |
7 |
45 |
0.344 |
185 |
165 |
|
|
XHVW2BK |
2 |
7 |
45 |
0.374 |
238 |
190 |
|
|
XHVW1BK |
1 |
19 |
55 |
0.426 |
301 |
220 |
|
|
XHVW1/0BK |
1/0 |
19 |
55 |
0.467 |
374 |
260 |
|
|
XHVW2/0BK |
2/0 |
19 |
55 |
0.512 |
465 |
300 |
|
|
XHVW3/0BK |
3/0 |
19 |
55 |
0.560 |
579 |
350 |
|
|
XHVW4/0BK |
4/0 |
19 |
55 |
0.619 |
723 |
405 |
|
|
XHVW250BK |
250 |
37 |
65 |
0.702 |
850 |
455 |
|
|
XHVW300BK |
300 |
37 |
65 |
0.759 |
997 |
500 |
|
|
XHVW350BK |
350 |
37 |
65 |
0.806 |
1,173 |
570 |
|
|
XHVW400BK |
400 |
37 |
65 |
0.851 |
1,314 |
615 |
|
|
XHVW500BK |
500 |
37 |
65 |
0.926 |
1,651 |
700 |
|
|
XHVW600BK |
600 |
61 |
80 |
1.047 |
1,972 |
780 |
|
|
XHVW750BK |
750 |
61 |
80 |
1.145 |
2,444 |
885 |
|
|
*Per NEC Table 310.15 (B)(17). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances. |
|||||||