SINGLE CONDUCTORS
SERVICEPRO-X®RW90600 Volt CopperNo Pulling Lubricant Required

Description
Single copper conductor, stranded and insulated with moisture, heat, and flame resistant, chemically crosslinked polyethylene. ServicePRO-X® Insulation–No Pulling Lubricant Required (#6 AWG and larger). Available in colors.
Application
Suitable for general purpose wiring, power distribution, and branch circuit wiring where a cable having superior flame retardance is required. Suitable for use in 105°C dry systems. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).
Standards
ASTM Standards: B-3 (soft or annealed), B-8 (concentric lay stranded),
B-787 (combination strand)
UL 44, CSA RW90: Certified by CSA for use in Canada
CSA C22.2 No. 38
ICEA S-95-658/NEMA WC-70
Flame Rated: CT Use (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant, Gasoline and Oil Resistant II
Appliance Wiring Material: Style 3578
RoHS Compliant
|
Part Number
|
Size (AWG or Kcmil) |
Strand (no.) |
Insulation Thickness (mils) |
Nominal Diameter Overall (in.) |
Approx. Net Weight (lb./1000') |
Ampacity* 90°C Wet/Dry |
|
|
XH14BK |
14 |
7 |
30 |
0.133 |
18 |
35† |
|
|
XH12BK |
12 |
7 |
30 |
0.152 |
27 |
40† |
|
|
XH10BK |
10 |
7 |
30 |
0.175 |
39 |
55† |
|
|
XH8BK |
8 |
7 |
45 |
0.233 |
64 |
80 |
|
|
XH6BK |
6 |
7 |
45 |
0.271 |
97 |
105 |
|
|
XH4BK |
4 |
7 |
45 |
0.320 |
149 |
140 |
|
|
XH3BK |
3 |
7 |
45 |
0.344 |
185 |
165 |
|
|
XH2BK |
2 |
7 |
45 |
0.374 |
230 |
190 |
|
|
XH1BK |
1 |
19 |
55 |
0.426 |
291 |
220 |
|
|
XH1/0BK |
1/0 |
19 |
55 |
0.467 |
366 |
260 |
|
|
XH2/0BK |
2/0 |
19 |
55 |
0.512 |
456 |
300 |
|
|
XH3/0BK |
3/0 |
19 |
55 |
0.560 |
569 |
350 |
|
|
XH4/0BK |
4/0 |
19 |
55 |
0.619 |
711 |
405 |
|
|
XH250BK |
250 |
37 |
65 |
0.702 |
835 |
455 |
|
|
XH300BK |
300 |
37 |
65 |
0.759 |
996 |
500 |
|
|
XH350BK |
350 |
37 |
65 |
0.806 |
1,155 |
570 |
|
|
XH400BK |
400 |
37 |
65 |
0.851 |
1,314 |
615 |
|
|
XH500BK |
500 |
37 |
65 |
0.926 |
1,631 |
700 |
|
|
XH600BK |
600 |
61 |
80 |
1.047 |
1,967 |
780 |
|
|
XH750BK |
750 |
61 |
80 |
1.145 |
2,441 |
885 |
|
|
*Per NEC Table 310.15 (B)(17). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances. |
|||||||