TRAY & POWER CABLES

TRAY CABLEXHHW-2 or RW90/EnviroPlus® 50% Ground600/1,000 Volt Copper, LSZH Jacket4 Conductor, Factory Mutual Group 1

Description

Four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled together with fillers (when necessary) and three bare copper ground conductors. Cable core is covered with binder tape and overall black low smoke, zero halogen, lead-free jacket.
Available with tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.

Standards

UL1277
CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL1685 and UL 1581, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: Black and Numbered (optional color codes available)
Low Smoke, Zero Halogen Jacket
RoHS Compliant
NEMA BABA 70901-2-2024 WC-02-03, WC-02-04, WC-02-05

VIEW PRODUCT DATA TABLE

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Insulation

Thickness
(mils)

Grounding

Conductors
(AWG)

Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight
(lb/1000')

Ampacity*
(30°C ambient) 90°C Wet/Dry

TCNH8/4G3#14

8

  7

45

(3) #14

  60

0.72

     384

  55

TCNH6/4G3#12

6

  7

45

(3) #12

  60

0.81

     577

  75

TCNH4/4G3#10

4

  7

45

(3) #10

  80

0.97

     887

  95

TCNH2/4G3#8

2

  7

45

(3) #8

  80

1.10

  1,306

130

TCNH1/4G3#8

1

19

55

(3) #8

  80

1.22

  1,594

145

TCNH1/04G3#6

1/0

19

55

(3) #6

  80

1.32

  2,011

170

TCNH2/04G3#6

2/0

19

55

(3) #6

  80

1.43

  2,415

195

TCNH3/04G3#4

3/0

19

55

(3) #4

  80

1.55

  3,049

225

TCNH4/04G3#4

4/0

19

55

(3) #4

110

1.75

  3,787

260

TCNH250/4G3#4

250

37

65

(3) #4

110

1.88

  4,330

290

TCNH350/4G3#2

350

37

65

(3) #2

110

2.12

  5,956

350

TCNH500/4G3#1

500

37

65

(3) #1

110

2.42

  8,206

430

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE