SINGLE CONDUCTORS
SERVICEPRO-X®USE-2 or RHW-2600/1,000 Volt Copper, VW-1, CT RatedNo Pulling Lubricant Required

Description
Single copper conductor, stranded and insulated with moisture and heat resistant, chemically crosslinked polyethylene. Featuring ServicePRO-X® Insulation–No Pulling Lubricant Required (#6 AWG and larger). Available in colors.
Application
Suitable for use in general purpose wiring applications and may be installed in raceway, conduit, direct burial, and aerial installations where a cable having superior flame retardance is required. Suitable for use in 105°C dry systems. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).
Standards
ASTM Standards: B-3 (soft or annealed), B-8 (concentric lay stranded),
B-787 (combination strand)
UL 44 and UL 854
ICEA S-95-658/NEMA WC-70
L-824C (#12 AWG - #4 AWG)
Federal Spec. A-A-59544
Flame Rated: VW-1 (all sizes), CT Use/IEEE 1202 (1/0 AWG and larger),
FT-4 (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant (#6 AWG and larger), Gasoline and Oil Resistant II
Direct Burial
RoHS Compliant
|
Part Number
|
Size (AWG or Kcmil) |
Strand (no.) |
Insulation Thickness (mils) |
Approx. Diameter Overall (in.) |
Approx. Net Weight (lb./1000') |
Ampacity* 90°C Wet/Dry |
|
|
USEVW14BK |
14 |
7 |
45 |
0.163 |
23 |
35† |
|
|
USEVW12BK |
12 |
7 |
45 |
0.182 |
32 |
40† |
|
|
USEVW10BK |
10 |
7 |
45 |
0.205 |
46 |
55† |
|
|
USEVW8BK |
8 |
7 |
60 |
0.263 |
73 |
80 |
|
|
USEVW6BK |
6 |
7 |
60 |
0.301 |
110 |
105 |
|
|
USEVW4BK |
4 |
7 |
60 |
0.350 |
164 |
140 |
|
|
USEVW3BK |
3 |
7 |
60 |
0.374 |
201 |
165 |
|
|
USEVW2BK |
2 |
7 |
60 |
0.404 |
248 |
190 |
|
|
USEVW1BK |
1 |
19 |
80 |
0.476 |
321 |
220 |
|
|
USEVW1/0BK |
1/0 |
19 |
80 |
0.517 |
395 |
260 |
|
|
USEVW2/0BK |
2/0 |
19 |
80 |
0.562 |
489 |
300 |
|
|
USEVW3/0BK |
3/0 |
19 |
80 |
0.610 |
605 |
350 |
|
|
USEVW4/0BK |
4/0 |
19 |
80 |
0.669 |
752 |
405 |
|
|
USEVW250BK |
250 |
37 |
95 |
0.762 |
902 |
455 |
|
|
USEVW300BK |
300 |
37 |
95 |
0.819 |
1,067 |
500 |
|
|
USEVW350BK |
350 |
37 |
95 |
0.866 |
1,217 |
570 |
|
|
USEVW400BK |
400 |
37 |
95 |
0.911 |
1,391 |
615 |
|
|
USEVW500BK |
500 |
37 |
95 |
0.986 |
1,702 |
700 |
|
|
USEVW600BK |
600 |
61 |
110 |
1.107 |
2,073 |
780 |
|
|
USEVW750BK |
750 |
61 |
110 |
1.205 |
2,554 |
885 |
|
|
*Per NEC Table 310.15 (B)(17). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances. |
|||||||