ARMORED CABLES
SERVICETECK® (TECK90)RW90/CPE1,000 Volt Copper3 Conductor

Description
Three or four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RW90 1kV), phase identified and cabled together with bare copper ground conductor(s). Cable core covered with mylar binder tape, inner jacket, aluminum interlocked armour, and outer CPE jacket.
Application
Suitable for use in exposed or concealed wiring in dry or wet locations, in ventilated or ladder type cable trays in dry or wet conditions, on walls or beams, directly buried.
Suitable for use in hazardous locations:
Class I - Groups A, B, C and D, Class II - Groups E, F and G, Class III - All Groups
Standards
UL 1569
C(UL) Teck 90: UL Listed/C(UL): Certified by UL for use in Canada
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4, Two-Hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight and Oil Resistant II Jacket
Direct Burial (includes encasement in concrete)
Colour Code: Method 4 (optional colour codes available)
RoHS Compliant
|
Part Number
|
Size (AWG or Kcmil) |
Strand (no.) |
Insulation Thickness (mils) |
Grounding Conductor (AWG) |
CPE Jacket Thickness Inner (mils) |
CPE Jacket Thickness Outer (mils) |
Diameter Inner Jacket
|
Diameter Armor
|
Diameter Overall
|
Approx. Net Weight (lb./1000') |
Ampacity* (90°C) |
|
CAAC8/3U |
8 |
7 |
60 |
10 |
50 |
50 |
0.69 |
0.89 |
0.99 |
519 |
55 |
|
CAAC6/3U |
6 |
7 |
60 |
8 |
50 |
50 |
0.77 |
0.97 |
1.07 |
699 |
75 |
|
CAAC4/3U |
4 |
7 |
60 |
8 |
50 |
50 |
0.88 |
1.09 |
1.19 |
913 |
95 |
|
CAAC3/3U |
3 |
7 |
60 |
6 |
50 |
50 |
0.94 |
1.15 |
1.25 |
1,082 |
115 |
|
CAAC2/3U |
2 |
7 |
60 |
6 |
50 |
50 |
1.00 |
1.27 |
1.37 |
1,283 |
130 |
|
CAAC1/3U |
1 |
19 |
80 |
6 |
50 |
50 |
1.15 |
1.43 |
1.53 |
1,575 |
145 |
|
CAAC1/03U |
1/0 |
19 |
80 |
6 |
50 |
60 |
1.24 |
1.51 |
1.63 |
1,885 |
170 |
|
CAAC2/03U |
2/0 |
19 |
80 |
6 |
50 |
60 |
1.33 |
1.61 |
1.73 |
2,222 |
195 |
|
CAAC3/03U |
3/0 |
19 |
80 |
4 |
50 |
60 |
1.44 |
1.71 |
1.83 |
2,680 |
225 |
|
CAAC4/03U |
4/0 |
19 |
80 |
4 |
50 |
60 |
1.56 |
1.83 |
1.95 |
3,195 |
260 |
|
CAAC250/3U |
250 |
37 |
95 |
4 |
60 |
60 |
1.78 |
2.09 |
2.21 |
3,783 |
290 |
|
CAAC350/3U |
350 |
37 |
95 |
3 |
60 |
75 |
2.01 |
2.29 |
2.44 |
5,025 |
350 |
|
CAAC500/3U |
500 |
37 |
95 |
2 |
60 |
75 |
2.30 |
2.57 |
2.72 |
6,755 |
430 |
|
CAAC600/3U |
600 |
61 |
110 |
2 |
75 |
75 |
2.56 |
2.85 |
3.00 |
8,123 |
475 |
|
*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances. |
|||||||||||