SERVICEDRIVE®
VFD JACKETED MC (ACWU90)RHW-2/CPE2,000 Volt Copper

Description
Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RHW-2), phase identified and cabled together with suitable fillers and three symmetrical bare copper ground conductors. Cable core shielded with 5-mil copper tape, helically applied with 50% overlap for 100% coverage and double tape thickness throughout the cable. Shielded core covered with galvanized steel interlocked armor with overall black CPE jacket. Available with aluminum armor or PVC or EnviroPlus® (LSZH) jacket. Available with 50% grounds*.
Application
For use in VFD applications.
Suitable for use in hazardous locations: Class I - Div 2,
Class II - Div 2, Class III - Div 1 and 2
*Patented for use with ServiceDrive® connector and termination kit.
Reference Materials
Standards
UL 1569, CSA C22.2 #51
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
UL 1685, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: Black and Numbered
RoHS Compliant
*U.S. Patent No. 7,309,835
|
Part Number
|
Size |
Strand |
Insulation Thickness |
Grounding Conductors |
Diameter Over Armor |
Jacket Thickness |
Approx. Diameter Overall |
Approx. Net Weight |
Ampacity** |
|
VFD2KGC14/3 |
14† |
7 |
60 |
(3) #14 |
0.63 |
50 |
0.73 |
376 |
25 |
|
VFD2KGC12/3 |
12† |
7 |
60 |
(3) #14 |
0.67 |
50 |
0.77 |
426 |
30 |
|
VFD2KGC10/3 |
10† |
7 |
60 |
(3) #14 |
0.73 |
50 |
0.83 |
496 |
40 |
|
VFD2KGC8/3 |
8† |
7 |
80 |
(3) #14 |
0.87 |
50 |
0.97 |
658 |
55 |
|
VFD2KGC6/3 |
6 |
7 |
80 |
(3) #12 |
0.95 |
50 |
1.05 |
836 |
75 |
|
VFD2KGC4/3 |
4 |
7 |
80 |
(3) #12 |
1.07 |
50 |
1.17 |
1,064 |
95 |
|
VFD2KGC3/3 |
3 |
7 |
80 |
(3) #10 |
1.11 |
50 |
1.21 |
1,234 |
110 |
|
VFD2KGC2/3 |
2 |
7 |
80 |
(3) #10 |
1.23 |
50 |
1.33 |
1,416 |
130 |
|
VFD2KGC1/3 |
1 |
19 |
95 |
(3) #10 |
1.37 |
50 |
1.47 |
1,806 |
150 |
|
VFD2KGC1/03 |
1/0 |
19 |
95 |
(3) #10 |
1.47 |
60 |
1.57 |
2,093 |
170 |
|
VFD2KGC2/03 |
2/0 |
19 |
95 |
(3) #10 |
1.57 |
60 |
1.69 |
2,470 |
195 |
|
VFD2KGC3/03 |
3/0 |
19 |
95 |
(3) #8 |
1.67 |
60 |
1.79 |
2,945 |
225 |
|
VFD2KGC4/03 |
4/0 |
19 |
95 |
(3) #8 |
1.81 |
60 |
1.93 |
3,478 |
260 |
|
VFD2KGC250/3 |
250 |
37 |
110 |
(3) #8 |
1.93 |
60 |
2.05 |
4,088 |
290 |
|
VFD2KGC350/3 |
350 |
37 |
110 |
(3) #6 |
2.17 |
60 |
2.29 |
5,359 |
350 |
|
VFD2KGC500/3 |
500 |
37 |
110 |
(3) #6 |
2.41 |
75 |
2.56 |
7,126 |
430 |
|
VFD2KGC600/3 |
600 |
61 |
125 |
(3) #6 |
2.65 |
75 |
2.80 |
8,372 |
475 |
|
VFD2KGC750/3 |
750 |
61 |
125 |
(3) #4 |
2.85 |
75 |
3.00 |
10,144 |
535 |
|
† UL Listed Only |
|||||||||