SINGLE CONDUCTORS
SERVICESOLAR® (PV)RHW-2/EnviroPlus®600 Volt Copper, LSZH Jacket

Description
Single copper conductor, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RHW-2) with an overall flame and sunlight resistant, low smoke, zero halogen, lead-free jacket.
Available with tinned conductors.
Application
Suitable for use as interconnection wiring on solar panels in grounded or ungrounded systems as defined in applicable parts of the National Electrical Code (NEC) NFPA 70, such as article 690.31(A).
Standards
UL 44 RHW-2, UL 854 USE-2, and UL 4703 PV Wire
C(UL) RPV90: CSA C22.2 #271
ICEA S-95-658/NEMA WC-70
Flame Rated: VW-1/FT-1, CT Use (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Low Smoke, Zero Halogen Jacket
RoHS Compliant
|
Part Number
|
Size (AWG or Kcmil) |
Strand (no.) |
Insulation Thickness (mils) |
Jacket Thickness (mils) |
Nominal Diameter Overall (in.) |
Approx. Net Weight (lb./1000') |
Ampacity* (30°C ambient) 90°C Wet/Dry |
|
PVENV16 |
16 |
26 |
45 |
30 |
0.21 |
26 |
8 |
|
PVENV14 |
14 |
7 |
45 |
30 |
0.22 |
33 |
25 |
|
PVENV12 |
12 |
7 |
45 |
30 |
0.24 |
43 |
30† |
|
PVENV10 |
10 |
7 |
45 |
30 |
0.27 |
58 |
40† |
|
PVENV8 |
8 |
7 |
60 |
30 |
0.32 |
87 |
55 |
|
PVENV6 |
6 |
7 |
60 |
45 |
0.39 |
135 |
75 |
|
PVENV4 |
4 |
7 |
60 |
45 |
0.44 |
192 |
95 |
|
PVENV3 |
3 |
7 |
60 |
45 |
0.46 |
231 |
115 |
|
PVENV2 |
2 |
7 |
60 |
45 |
0.49 |
279 |
130 |
|
PVENV1 |
1 |
19 |
80 |
60 |
0.60 |
373 |
145 |
|
PVENV1/0 |
1/0 |
19 |
80 |
60 |
0.64 |
454 |
170 |
|
PVENV2/0 |
2/0 |
19 |
80 |
60 |
0.68 |
552 |
195 |
|
PVENV3/0 |
3/0 |
19 |
80 |
60 |
0.73 |
673 |
225 |
|
PVENV4/0 |
4/0 |
19 |
80 |
60 |
0.79 |
824 |
260 |
|
PVENV250 |
250 |
37 |
95 |
80 |
0.89 |
996 |
290 |
|
PVENV300 |
300 |
37 |
95 |
80 |
0.94 |
1,166 |
320 |
|
PVENV350 |
350 |
37 |
95 |
80 |
0.99 |
1,336 |
350 |
|
PVENV400 |
400 |
37 |
95 |
80 |
1.04 |
1,503 |
380 |
|
PVENV500 |
500 |
37 |
95 |
80 |
1.12 |
1,837 |
430 |
|
PVENV600 |
600 |
61 |
110 |
80 |
1.22 |
2,192 |
475 |
|
PVENV750 |
750 |
61 |
110 |
80 |
1.32 |
2,687 |
535 |
|