ARMORED CABLES

SERVICETECK® (TECK90)

RW90/CPE

1,000 Volt Copper

Single Conductor

Description

Single copper conductor, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RW90 1kV), a served concentric ground and covered with mylar binder tape, inner jacket, aluminum interlocked armour, and outer CPE jacket.

Application

Suitable for use in exposed or concealed wiring in dry or wet locations, in ventilated or ladder type cable trays in dry or wet conditions, on walls or beams, directly buried.
Suitable for use in hazardous locations: Class I - Groups A, B, C and D,
       Class II - Groups E, F and G, Class III - All Groups

Standards

UL 1569
C(UL) Teck 90: UL Listed/C(UL): Certified by UL for use in Canada
CSA C22.2 #131/#174
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), ICEA T-30-520 (70,000 BTU),
       IEEE 1202/CSA FT-4, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight and Oil Resistant II Jacket
Direct Burial (includes encasement in concrete)
RoHS Compliant

 

VIEW PRODUCT DATA TABLE

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation

Thickness

(mils)

Grounding

Conductor

(AWG)

CPE Jacket

Thickness

Inner (mils)

CPE Jacket

Thickness

Outer (mils)

Diameter

Inner Jacket

 

Diameter

Armor

 

Diameter

Overall

 

Approx.

Net Weight

(lb./1000')

Ampacity*

(90°C)

CAAC6U

6

  7

60

  8

50

50

0.52

0.73

0.83

     370

 115

CAAC4U

4

  7

60

  6

50

50

0.57

0.77

0.87

     469

 140

CAAC3U

3

  7

60

  6

50

50

0.60

0.81

0.91

     519

165

CAAC2U

2

  7

60

  6

50

50

0.63

0.83

0.93

     574

190

CAAC1U

1

19

80

  4

50

50

0.70

0.91

1.01

     718

220

CAAC1/0U

1/0

19

80

  4

50

50

0.73

0.95

1.05

     809

260

CAAC2/0U

2/0

19

80

  4

50

50

0.78

0.99

1.09

     916

300

CAAC3/0U

3/0

19

80

  3

50

50

0.90

1.11

1.21

  1,108

350

CAAC4/0U

4/0

19

80

  3

50

50

0.95

1.23

1.33

  1,279

405

CAAC250U

250

37

95

  2

50

50

1.05

1.33

1.43

  1,515

455

CAAC350U

350

37

95

  1

50

50

1.15

1.43

1.53

  1,936

570

CAAC500U

500

37

95

  1/0

50

60

1.29

1.57

1.69

  2,572

700

CAAC750U

750

61

110

  2/0

50

60

1.50

1.79

1.91

  3,566

885

*Per NEC Table 310.15 (B)(16). NOTE: The data shown is approximate and subject to standard industry tolerances.

 

 