Single Conductors
XHHW-2
CT Rated
600 Volt Copper
Applications: Type XHHW-2, CT is suitable for general purpose wiring, for power distribution and branch circuit wiring, where a cable having superior flame retardance is required. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).
Description: Single copper conductor, stranded, insulated with moisture, heat, and flame resistant, chemically cross-linked polyethylene insulation. Temperature rating 90° C in wet and dry locations. Colors available.
Standards:
UL 44, ICEA S-95-658/NEMA WC-70
Federal spec A-A-59544, 90° C Wet/Dry
CT use 1/0 and larger
Gasoline and Oil Resistant II
C(UL)US: CSA/UL Listed
Sunlight Resistant
-40° C rated
XHHW-2
VW-1, CT Rated
600 Volt Copper
Applications: Type XHHW-2, VW-1 is suitable for general purpose wiring, for power distribution and branch circuit wiring, where a cable having superior flame retardance is required. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).
Description: Single copper conductor, stranded, insulated with moisture, heat, and flame resistant, chemically cross-linked polyethylene insulation. Temperature rating 90° C in wet and dry locations. All sizes pass the vertical flame test (VW-1). Colors available.
Standards:
UL 44, ICEA S-95-658/NEMA WC-70
Federal spec A-A-59544, 90° C Wet/Dry
For CT Use / IEEE 1202 1/0 AWG and larger
Gasoline and Oil Resistant II
C(UL)US: CSA/UL Listed
Sunlight Resistant (Black only)
-40° C rated
XLP USE-2 or RHH/RHW-2
CT Rated
600 Volt, Copper
Applications: Types USE-2, RHH/RHW-2 CT are suitable for use in general purpose wiring applications and may be installed in raceway, conduit, direct burial and aerial installations where a cable having superior flame retardance is required.
Description: Single copper conductor, stranded, insulated with moisture and heat resistant, chemically cross-linked polyethylene insulation. Temperature rating 90° C in wet and dry applications. Colors available.
Standards:
UL 44 and UL 854, ICEA S-95-658/NEMA WC-70
C(UL) US: CSA/UL Listed
600 Volt UL/1000 Volt CSA
#14 - 4/0 Rated L-824C
Federal spec. A-A-59544
CT Use 1/0 and Larger
Gasoline and Oil Resistant II
-40° C rated
Direct Burial/Sunlight Resistant
XLP USE-2 or RHH/RHW-2
VW-1, CT Rated
600 Volt, Copper
Applications: Types USE-2, RHH/RHW-2 VW-1 are suitable for use in general purpose wiring applications and may be installed in raceway, conduit, direct burial and aerial installations where a cable having superior flame retardance is required.
Description: Single copper conductor, stranded, insulated with moisture and heat resistant, chemically cross-linked polyethylene insulation. Temperature rating 90° C in wet and dry applications. All sizes pass the vertical flame test (VW-1). Colors available.
Standards:
UL 44 and UL 854, ICEA S-95-658/NEMA WC-70
Federal spec. A-A-59544
600 Volt UL / 1000 Volt CSA
#14-4/0 rated L-824C
For CT Use / IEEE 1202 1/0 AWG and larger
Gasoline and Oil Resistant II
-40° C rated
Direct Burial
C(UL)US: CSA/UL Listed
Sunlight Resistant (Black only)
Type RHH/RHW-2
2000 Volt, Copper
Applications: Type RHH, RHW-2 is suitable for wiring in raceways, conduit, etc. Applications include general purpose wiring for power distribution, services, feeders, and branch circuit wiring in residential, industrial, and commercial buildings.
Description: Single copper conductor, stranded, insulated with moisture and heat resistant cross-linked polyethylene. Temperature rating is 90° C in wet and dry applications.
Standards:
UL 44 and UL 854
Federal Spec. A-A-59544
ICEA S-95-658/NEMA WC-70
CT rated 1/0 and larger
Sunlight Resistant
#14-4/0 Rated L-824C
-40° C rated
Suitable for use in 105° C Dry System
UL 4703 Photovoltaic for 1000 volt systems.
|

XHHW-2 CT Rated 600 Volt Copper

XHHW-2 VW-1, CT Rated 600 Volt Copper

XLP USE-2 or RHH/RHW-2 CT
Rated 600 Volt, Copper

XLP USE-2 or RHH/RHW-2 VW-1,
CT Rated 600 Volt, Copper

Type RHH/RHW-2 2000 Volt, Copper
|