Twisted / Aerial Cables
Preassembled Aerial Cable
600 Volt
Copper XHHW-2
Description: 3 or 4 conductors, stranded, bare annealed copper, insulated with heat and moisture resistant cross-linked polyethylene. The conductors shall be cabled with a left hand lay and a messenger of 30% EHS copperweld shall be laid parallel and bound with a flat bare copper binding strap. Available with aluminum conductors.
Standards:
ICEA S-95-658/NEMA WC-70
Single CDRS are UL 44 Listed
Note: Optional constructions include: galvanized or stainless steel messengers, PVC coated copper, stainless steel strap.
Preassembled Aerial Cable
2.4kV Nonshielded
Copper EPR
Applications: Where NEC jurisdiction applies: 2,400 volt nonshielded power cable, Type MV-105 Dry, for conductor temperatures not exceeding 105º C in dry locations.
Description: Class B stranded copper, extruded conductor shield, insulated with heat and moisture resistant EPR. The conductors shall be cabled with a left hand lay and laid parallel to a 30% EHS copperweld messenger then bound with a flat copper binding strap.
Standards:
ICEA S-96-659/NEMA WC-71
Single CDRS are UL-1072 Listed
Note: Optional constructions include: galvanized or stainless steel messengers, stainless steel strap.
Preassembled Aerial Cable
5kV Shielded
Copper EPR
Description: Class B stranded copper, extruded conductor shield, insulated with heat and moisture resistant EPR, semi-conducting insulation shield, copper shield (stranded or tape), overall PVC jacket. The conductors shall be cabled with a left hand lay and laid parallel to a 30% EHS copperweld messenger then bound with a flat PVC coated copper binding strap.
Standards:
ICEA S-93-639/NEMA WC-74
Single CDRS are UL-1072 Listed
Note: Optional constructions include: galvanized or stainless steel messengers, PVC coated stainless steel strap.
Preassembled Aerial Cable
15 kV MV-105
133% 15,000 Volt
Copper EPR
Description: 3 copper conductors, Class B strand, annealed copper, heat and moisture resistant ethylene polypropylene rubber, semi-conducting insulation shield, (wire or tape) conductor shield, type EPR, 133% insulation level, polyvinyl chloride jacket. The conductors shall be cabled with a left hand lay and laid parallel to the 30% EHS copperweld messenger, bound with a rounded-edge flat PVC coated copper binding strap.
Standards:
ICEA S-93-639/NEMA WC-74
Single CDRS are UL 1072 Listed
Note: Optional constructions include: galvanized or stainless steel messengers, PVC coated, stainless steel strap.
|