ARMORED CABLES

SERVICETECK® (TECK90)XHHW-2 or RW90/PVC600 Volt Copper

Description

Class B stranded copper conductors, insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled together with **bare copper ground conductor. Cable core covered with mylar binder tape, inner PVC jacket, aluminum interlocked armor, and outer PVC jacket.
**Cable with seven conductors or more will have a green insulated ground.

Application

Suitable for use in exposed or concealed wiring in dry or wet locations, in ventilated or ladder type cable trays in dry or wet conditions, on walls or beams, or directly buried.

Suitable for use in hazardous locations: Class I - Groups A, B, C and D,
Class II - Groups E, F and G, Class III - All Groups.

Standards

UL 1569
C(UL) Teck 90: UL Listed/C(UL): Certified by UL for use in Canada
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU),
       FT-4 Flame Test, IEEE 1202/CSA FT-4, Two-Hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -25°C
Sunlight Resistant, Gasoline and Oil Resistant II Jacket
Direct Burial (includes encasement in concrete)
Color Code: K-2 Solid Colors (3 and 5-19 conductor),
       K-2 Solid Colors and Neutral White (2 and 4 conductor)
RoHS Compliant

 

VIEW PRODUCT TABLE DATA

Part Number

 

Number of

Conductors

 

Grounding

Conductor
(AWG)

PVC Jacket

Thickness

Inner
(mils)

PVC Jacket

Thickness

Outer
(mils)

Diameter

Inner Jacket

 

Diameter

Armor

 

Diameter

Overall

 

Approx.

Net Weight
(lb./1000')

Ampacity*
(30°C ambient) 90°C Wet/Dry

PAAP14/2

  2

14

50

50

0.39

0.59

0.69

   214

  25†

PAAP14/3

  3

14

50

50

0.41

0.61

0.71

   239

  25†

PAAP14/4

  4

14

50

50

0.44

0.65

0.75

   271

  20†

PAAP14/5

  5

14

50

50

0.48

0.69

0.79

   303

  20†

PAAP14/7

  7

14

50

50

0.56

0.77

0.87

   372

  17†

PAAP14/9

  9

14

50

50

0.64

0.85

0.95

   436

  17†

PAAP14/12

12

14

50

50

0.69

0.89

0.99

   505

12

PAAP14/19

19

14

50

50

0.80

1.01

1.11

   673

12

 

PAAP12/2

  2

12

50

50

0.42

0.63

0.73

   253

  30†

PAAP12/3

  3

12

50

50

0.45

0.65

0.75

   287

  30†

PAAP12/4

  4

12

50

50

0.49

0.69

0.79

   328

  24†

PAAP12/5

  5

12

50

50

0.53

0.73

0.83

   369

  24†

PAAP12/7

  7

12

50

50

0.62

0.83

0.93

   464

  21†

PAAP12/9

  9

12

50

50

0.71

0.91

1.01

   547

  21†

PAAP12/12

12

12

50

50

0.77

0.97

1.07

   648

15

PAAP12/19

19

12

50

50

0.89

1.09

1.19

   878

15

 

PAAP10/2

  2

10

50

50

0.47

0.67

0.77

   306

  40†

PAAP10/3

  3

10

50

50

0.50

0.71

0.81

   358

  40†

PAAP10/4

  4

10

50

50

0.54

0.75

0.85

   413

  32†

PAAP10/5

  5

10

50

50

0.59

0.79

0.89

   467

  32†

PAAP10/7

  7

10

50

50

0.70

0.91

1.01

   595

28

PAAP10/9

  9

10

50

50

0.80

1.01

1.11

   710

28

PAAP10/12

12

10

50

50

0.87

1.07

1.17

   851

20

PAAP10/19

19

10

50

50

1.01

1.27

1.37

1,208

20

*Per NEC Table 310.15 (B)(16). NOTE: The data shown is approximate and subject to standard industry tolerances.

 

 

REQUEST QUOTE