TWISTED CABLES

SERVICE DROPXHHW-2 or RW90600/1,000 Volt Copper

Description

Multiple soft drawn copper conductors, stranded and insulated with heat, moisture, and sunlight resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90). Neutral is solid or stranded bare, hard drawn copper.

Standards

ASTM Standards: B-1 (hard drawn), B-3 (soft drawn or annealed),
      
B-8 (concentric-lay strand), B-787 (combination unilay)
UL 44
ICEA S-95-658/NEMA WC-70
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
RoHS Compliant

VIEW PRODUCT DATA TABLE

Part Number

 

Code Name

 

Insulated Conductors Size
(AWG or Kcmil)

Insulated Conductors
Strand (no.)

Insulated Conductors

Insulation Thickness
(mils)

Neutral - Messenger Size

HARD DRAWN
(AWG)

Neutral - Messenger
Strand (no.)

Approx. Net Weight
(lb./1000')

Ampacity*
(40°C ambient)

TRI8CUSOL

Bodoni

8

  7

45

8

  1

   180

  66

TRI8CU

Garamond

8

  7

45

8

  7

   182

  66

TRI6CUSOL

Futura

6

  7

45

6

  1

   276

  89

TRI6CU

Gothic

6

  7

45

6

  7

   281

  89

TRI4CUSOL

Ionic

4

  7

45

4

  1

   427

117

TRI4CU

Caslon

4

  7

45

4

  7

   435

117

TRI2CU

Century

2

  7

45

2

  7

   678

158

TRI1/0CU

Corinthian

1/0

19

55

1/0

  7

1,077

214

TRI2/0CU

Doric

2/0

19

55

2/0

  7

1,348

247

TRI3/0CU

Tuscan

3/0

19

55

3/0

  7

1,688

287

TRI4/0CU

Composite

4/0

19

55

4/0

  7

2,130

335

TRI250CU

Roman

250

37

65

250

37

2,484

374

TRI350CU

Helvetica

350

37

65

350

37

3,451

464

TRI500CU

Deville

500

37

65

500

37

4,894

580

 

QUAD8CU

Huntington

8

  7

45

8

  7

   247

  66

QUAD6CUSOL

Atlanta

6

  7

45

6

  1

   373

  89

QUAD6CU

Tallahassee

6

  7

45

6

  7

   379

  89

QUAD4CUSOL

Baton Rouge

4

  7

45

4

  1

   576

117

QUAD4CU

Richmond

4

  7

45

4

  7

   587

117

QUAD2CUSOL

Jackson

2

  7

45

2

  1

   896

158

QUAD2CU

Seattle

2

  7

45

2

  7

   912

158

QUAD1/0CU

Nashville

1/0

19

55

1/0

  7

1,450

214

QUAD2/0CU

Lincoln

2/0

19

55

2/0

  7

1,813

247

QUAD3/0CU

Raleigh

3/0

19

55

3/0

  7

2,268

287

QUAD4/0CU

Denver

4/0

19

55

4/0

  7

2,855

335

QUAD250CU

Pittsburgh

250

37

65

250

37

3,333

374

QUAD350CU

Houston

350

37

65

350

37

4,624

464

QUAD500CU

Culloden

500

37

65

500

37

6,553

580

*Per NEC Table 310.15 (B)(20). Ampacity figures are based on conductor temperature of 90°C, ambient temperature of 40°C. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE