TRAY & POWER CABLES

TRAY CABLERW90/EnviroPlus®1,000 Volt Copper, LSZH Jacket3 Conductor, Factory Mutual Group 1

Description

Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type USE-2 or RW90 1kV), phase identified and cabled together with fillers and bare copper ground conductor. Cable core is covered with binder tape and overall black low smoke, zero halogen, lead-free jacket.
Available with tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2

Standards

UL1277
CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4
       UL1685 and UL 1581, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: Method 4 (optional color codes available)
Low Smoke, Zero Halogen Jacket
RoHS Compliant

VIEW PRODUCT DATA TABLE

 

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Insulation

Thickness
(mils)

Grounding

Conductor
(AWG)

Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight
(lb./1000')

Ampacity*
(30°C ambient)

90°C Wet/Dry

TCE8/3UG

8

  7

  60

10

  60

0.72

       329

  55

TCE6/3UG

6

  7

  60

  8

  60

0.81

       490

  75

TCE4/3UG

4

  7

  60

  8

  80

0.95

       715

  95

TCE3/3UG

3

  7

  60

  6

  80

1.00

       868

115

TCE2/3UG

2

  7

  60

  6

  80

1.07

    1,028

130

TCE1/3UG

1

19

  80

  6

  80

1.22

    1,287

145

TCE1/03UG

1/0

19

  80

  6

  80

1.31

    1,551

170

TCE2/03UG

2/0

19

  80

  6

  80

1.41

    1,866

195

TCE3/03UG

3/0

19

  80

  4

  80

1.51

    2,299

225

TCE4/03UG

4/0

19

  80

  4

  80

1.64

    2,790

260

TCE250/3UG

250

37

  95

  4

110

1.83

    3,347

290

TCE350/3UG

350

37

  95

  3

110

2.05

    4,472

350

TCE500/3UG

500

37

  95

  2

110

2.32

    6,126

430

TCE600/3UG

600

61

110

  2

110

2.54

    7,285

475

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE